ASL INTERCOM VAR8-ACU Series Manual

Busca en linea o descarga Manual para Redes ASL INTERCOM VAR8-ACU Series. ASL INTERCOM VAR8-ACU Series Product manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 52
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
EAP01
Emergency Announcement Point
ASL Document Ref.: U-0464-0530.doc
Issue: 03 complete, approved - Date: 13/08/10
Part Number: M0464_114
Product Manual
Vista de pagina 0
1 2 3 4 5 6 ... 51 52

Indice de contenidos

Pagina 1 - Emergency Announcement Point

EAP01Emergency Announcement PointASL Document Ref.: U-0464-0530.docIssue: 03 complete, approved - Date: 13/08/10Part Number: M0464_114Product Manual

Pagina 2 - Page 2 of 52

EAP01 - Product Manual 3 Installation 3.1 EAP01 Components Figure 2 EAP01 Main Components THE LAST SECTION OF THE BARCODE AFTERTHE SECOND FORWARD S

Pagina 3 - Contents

EAP01 - Product Manual Figure 3 EAP01 Front Panel/Electronics Assembly DIP SWITCH (NOT USED) 14-WAY DUAL CONNECTOR (NOT USED) 4xLEDs (NOT USED) 1 32

Pagina 4 - Page 4 of 52

EAP01 - Product Manual 3.2 Installation Requirements 3.2.1 Equipment and Tool Requirements • The EAP01 unit. • Suitable cable glands/conduit fixing

Pagina 5 - 1 Description

EAP01 - Product Manual 3.3 Recommended Installation Procedure Please read and observe the “Safety and Precautions” section on page 46 of this ma

Pagina 6 - 2 Operation

EAP01 - Product Manual 3. The EAP01 front panel/electronics assembly is normally supplied disconnected from the back box in a separate box. When the

Pagina 7 - Page 7 of 52

EAP01 - Product Manual 4. Drill holes in the back box for cable gland or conduit entry and wall mounting, according to the particular installation c

Pagina 8 - PRESS AND HOLD

EAP01 - Product Manual 8. Feed the installation cables into the unit through the cable glands or conduit. Figure 7 gives an indication of the length

Pagina 9 - IN PROGRESS

EAP01 - Product Manual 12. Ensure that the power supply disconnect terminal is toggled on, if provided, as shown in Figure 8. The power supply disco

Pagina 10 - 3 Installation

EAP01 - Product Manual 14. Reconnect the front panel assembly as follows, see Figure 5: a. Plug the flying leads to the multi-way connectors on the

Pagina 11 - Page 11 of 52

EAP01 - Product Manual 4 Connections 4.1 DIN Rail Terminal Allocation Table 1 EAP01 Terminal Allocation Terminal Connection Description 1 AUDIO +

Pagina 12 - 3.2.2 Cabling Requirements

EAP01 - Product Manual Copyright © 2008 Application Solutions (Safety and Security) Ltd. Application Solutions (Safety and Security) Ltd. Unit 1

Pagina 13 - Page 13 of 52

EAP01 - Product Manual 4.2 Connection Diagrams For BS5839 Pt.8 compliance the EAP01 should be connected to Router’s inputs 1 or 2, which operate

Pagina 14 - BS VERSION < 5

EAP01 - Product Manual 4.2.1 Connection to VAR4/VAR12/VAR20 Input 1 The following diagram shows the connection of the EAP01 to the VAR4/VAR12/VAR20’

Pagina 15 - Page 15 of 52

EAP01 - Product Manual 4.2.2 Connection to VAR4/VAR12/VAR20 Input 2 The following diagram shows the connection of the EAP01 to a VAR4/VAR12/VAR20’s

Pagina 16 - PPROX. 250 MM

EAP01 - Product Manual 4.2.3 Connection to ACU or VAR8-ACU Inputs 1 or 2 The following diagram shows the connection of the EAP01 to an ACU’s or VAR8

Pagina 17 - (TOGGLED ON)

EAP01 - Product Manual 4.2.4 Connection to DAU or VAR8 Inputs 1 or 2 The following diagram shows the connection of the EAP01 to a DAU’s or VAR8’s Mi

Pagina 18 - Page 18 of 52

EAP01 - Product Manual 5 Commissioning the EAP01 For operational details refer to your system specific documentation; see Table 5 (page 48). L The

Pagina 19 - 4 Connections

EAP01 - Product Manual 5.3 Configuring the Microphone Audio Parameters 5.3.1 Microphone Input Gain VAR4/12/20 Menu: ConfigurationÆSystemÆRouterÆInpu

Pagina 20 - 4.2 Connection Diagrams

EAP01 - Product Manual The detection threshold level is adjustable as follows. 1. Configure Mode=LF and Level (dB)=–40, enabling the Router to dete

Pagina 21 - Page 21 of 52

EAP01 - Product Manual 2. Ensure that the Night Time Volume Control is inactive, by setting it to ‘Off’: Menu: ConfigurationÆSystemÆRouterÆNoiseÆOff

Pagina 22 - Page 22 of 52

EAP01 - Product Manual 5.3.5 Microphone Fade Up and Down Times Menu: ConfigurationÆSystemÆRouterÆInputsÆMic/LineÆ<I/P #nn – input name> ÆFire

Pagina 23 - Page 23 of 52

EAP01 - Product Manual Issue: 02 complete, approved Page 3 of 52 Contents 1 Description ...

Pagina 24 - Page 24 of 52

EAP01 - Product Manual Figure 15 Sequence of Events for Paging Microphone Chime Overriding a Background Music MUSICFADE UP=T1FADE DOWN= T2T4T1MICROP

Pagina 25 - 5 Commissioning the EAP01

EAP01 - Product Manual 5.4 Configuring the Microphone Control Parameters 5.4.1 Microphone Priority Menu: ConfigurationÆSystemÆRouterÆInputsÆMic/LineÆ

Pagina 26 - 5.3.1 Microphone Input Gain

EAP01 - Product Manual 5.4.2 Microphone Class Menu: ConfigurationÆSystemÆRouterÆInputsÆMic/LineÆ<I/P #nn – input name> ÆFire MicrophoneÆCtrlÆPr

Pagina 27 - Page 27 of 52

EAP01 - Product Manual 5.4.4 Busy and Select Indication LEDs Mode (ACU and VAR8-ACU only) Menu: ConfigurationÆSystemÆRouterÆInputsÆMic/LineÆ<I/P

Pagina 28 - Page 28 of 52

EAP01 - Product Manual 6 Fault Finding Table 2 EAP01 Faults – VAR4/12/20 Operational Fault Symptom Fault Description Fault Code(s) Reported and Log

Pagina 29 - FADE DOWN= T2

EAP01 - Product Manual Table 3 EAP01 Faults – Intellevac Units (ACU and DAU), VAR8, and VAR8-ACU Operational Fault Symptom Fault Description Fault

Pagina 30 - Page 30 of 52

EAP01 - Product Manual 7 Maintenance The EAP01 should be tested with the PA/VA system for correct operation on a weekly basis as part of the fire and

Pagina 31 - 5.4.1 Microphone Priority

EAP01 - Product Manual 7.2.2 Power Supply via Signal Terminal Power the EAP01 on or off by connecting or disconnecting the power supply wiring from

Pagina 32 - 5.4.3 Microphone Name

EAP01 - Product Manual 7.3 Removing the EAP01 Front Panel/Electronics Assembly For maintenance purposes the EAP01’s preferred Line Replaceable Unit

Pagina 33 - Page 33 of 52

EAP01 - Product Manual 5. Disconnect the EAP01 front panel assembly by unplugging the flying leads from the multi-way connectors on the electronics

Pagina 34 - 6 Fault Finding

EAP01 - Product Manual Issue: 02 complete, approved Page 4 of 52 11 Spare Parts ...

Pagina 35 - EAP01 - Product Manual

EAP01 - Product Manual 7.4 Installing the EAP01 Front Panel/Electronics Assembly The following procedure describes how to install the EAP01 Front Pa

Pagina 36 - 7 Maintenance

EAP01 - Product Manual 2. Power the unit on as described in Section “7.2 Powering the EAP01 On and Off” (page 36). 3. Fix the front panel assembly

Pagina 37 - Page 37 of 52

EAP01 - Product Manual 7.5 EAP01 Front Panel/Electronics Assembly Replacement The replacement of the EAP01 front panel and the electronics assembly

Pagina 38 - Page 38 of 52

EAP01 - Product Manual 7.6 PTT Function Test Measurement of the resistance between PTT+ and PTT– may not be possible unless the unit is powered, dep

Pagina 39

EAP01 - Product Manual 8 Product Specification General Supply Voltage Range...

Pagina 40

EAP01 - Product Manual 9 Mechanical Dimensions Figure 22 Mechanical Dimensions 151.5 mmSIDE VIEW151.5 mmTOP VIEW100 mm50 mm25 mm151.5 mmBOTTOM VIEW5

Pagina 41 - Page 41 of 52

EAP01 - Product Manual 10 Safety and Precautions 10.4 Unpacking and Handling The equipment should be unpacked and inspected immediately on receipt.

Pagina 42 - Page 42 of 52

EAP01 - Product Manual 11 Spare Parts Table 4 EAP01 Spare Part List ASL Part Number Additional Information A0464611 Complete front panel and elect

Pagina 43 - 7.6 PTT Function Test

EAP01 - Product Manual 12 Reference Documents Additional reference information may be found in the following documentation, available from the “Data

Pagina 44 - 8 Product Specification

EAP01 - Product Manual 13 Index A announcement chime...7, 8 priority ...

Pagina 45 - 9 Mechanical Dimensions

EAP01 - Product Manual 1 Description The EAP01 Emergency Announcement Point is housed in an IP65 vandal resistant, lockable wall-mounting box. It is

Pagina 46 - Precautions

EAP01 - Product Manual This page intentionally left blank. Issue: 02 complete, approved Page 50 of 52

Pagina 47 - 11 Spare Parts

EAP01 - Product Manual Service and Warranty Name and Address of Authorised Distributor: This product carries a full warranty. For full details

Pagina 49 - 13 Index

EAP01 - Product Manual 2 Operation 2.1 Control and Indicators Figure 1 EAP01 Front Panel MANUFACTURED IN THE UKBY APPLICATION SOLUTIONS LTDEAP01SPE

Pagina 50

EAP01 - Product Manual 1 Fist Microphone with integral PTT button When the PTT button is pressed it activates the All-Call zone selection, opens the

Pagina 51 - Service and Warranty

EAP01 - Product Manual 2.2 Live Announcements via the Fist Microphone 1. Access the internal front panel by unlocking and opening the cabinet do

Pagina 52

EAP01 - Product Manual ONSPEAK NOWLOUDSPEAKERANNOUNCEMENTIN PROGRESS 6. When the chime has finished (if programmed at the Router), the SPEAK NOW LE

Comentarios a estos manuales